Siemens SIMATIC (ICSA-26-321-08)
- Command
- CYBERCOM
- Region
- Cyber
- Category
- Cyber threat
- Source
- CISA Cybersecurity Advisories
At a glance
- What
- Cyber Threat
- Who
- CISA Cybersecurity Advisories
- When
- Nov 17, 2026 at 12:00 PM UTC
Statement from CISA Cybersecurity Advisories, November 17.
Summary
The products listed below contain an authentication bypass vulnerability that could allow an on-path attacker to take over the session of a legitimate user and execute arbitrary code with the privileges of the victim user. Siemens is preparing fixes and recommends specific mitigations for products where fixes are not or not yet available.
The following versions of Siemens SIMATIC are affected:
SIMATIC Batch V9.1 vers:all/* (CVE-2026-58114)
SIMATIC Information Server 2020 vers:all/* (CVE-2026-58114)
SIMATIC Information Server 2022 vers:all/* (CVE-2026-58114)
SIMATIC PCS 7 V9.1 vers:all/* (CVE-2026-58114)
SIMATIC Process Historian 2020 vers:all/* (CVE-2026-58114)
SIMATIC Process Historian 2022 vers:all/* (CVE-2026-58114)
SIMATIC WinCC Runtime Professional V17 vers:all/* (CVE-2026-58114)
SIMATIC WinCC Runtime Professional V18 vers:all/* (CVE-2026-58114)
SIMATIC WinCC Runtime Professional V19 vers:all/* (CVE-2026-58114)
SIMATIC WinCC Runtime Professional V20 vers:all/* (CVE-2026-58114)
SIMATIC WinCC Runtime Professional V21 vers:all/* (CVE-2026-58114)
SIMATIC WinCC V7.5 vers:all/* (CVE-2026-58114)
SIMATIC WinCC V8.0 vers:all/* (CVE-2026-58114)
SIMATIC WinCC V8.1 vers:all/* (CVE-2026-58114)
CVSS
Vendor
Equipment v3 7.5
Siemens
SIMATIC batch V9.1
1 Vulnerability
Weak Authentication
Background
Critical Infrastructure Sectors: Critical Manufacturing
Countries/Areas Deployed: Worldwide
Company Headquarters Location: Germany
Vulnerabilities
CVE-2026-58114
Affected systems do not properly secure their remote user authentication with the deprecated NTLM protocol. This could allow unauthenticated remote attackers, who have achieved a machine in the middle position, to relay NTLM authentication and impersonate a legitimate user. The potential impact depends on the services that are accessible, e.g. a SQL server used by WinCC.
Read More
14 Affected Products
SIMATIC batch V9.1
Product Status: known_affected
Remediations
Mitigation
No fix planned
Currently no fix is planned
SIMATIC WinCC Runtime Professional V20
Product Status: known_affected
Remediations
Mitigation
None available
Currently no fix is available
SIMATIC WinCC Runtime Professional V21
Product Status: known_affected
Remediations
Mitigation
None available
Currently no fix is available
SIMATIC WinCC V7.5
Product Status: known_affected
Remediations
Mitigation
None available
Currently no fix is available
SIMATIC WinCC V8.0
Product Status: known_affected
Remediations
Mitigation
None available
Currently no fix is available
SIMATIC WinCC V8.1
Product Status: known_affected
Remediations
Mitigation
None available
Currently no fix is available
SIMATIC Information Server 2020
Product Status: known_affected
Remediations
Mitigation
No fix planned
Currently no fix is planned
SIMATIC Information Server 2022
Product Status: known_affected
Remediations
Mitigation
No fix planned
Currently no fix is planned
SIMATIC PCS 7 V9.1
Product Status: known_affected
Remediations
Mitigation
No fix planned
Currently no fix is planned
SIMATIC Process Historian 2020
Product Status: known_affected
Remediations
Mitigation
No fix planned
Currently no fix is planned
SIMATIC Process Historian 2022
Product Status: known_affected
Remediations
Mitigation
No fix planned
Currently no fix is planned
SIMATIC WinCC Runtime Professional V17
Product Status: known_affected
Remediations
Mitigation
None available
Currently no fix is available
SIMATIC WinCC Runtime Professional V18
Product Status: known_affected
Remediations
Mitigation
None available
Currently no fix is available
SIMATIC WinCC Runtime Professional V19
Product Status: known_affected
Remediations
Mitigation
None available
Currently no fix is available
Additional Metrics
Relevant CWE: CWE-1390 Weak Authentication
CVSS Version
Base Score
Base Severity
Vector String
3.1
7.5
High
CVSS:3.1/av:N/ac:H/PR:N/ui:R/S:U/C:H/I:H/a:H
View CVE Details
Acknowledgments
Siemens ProductCERT reported this vulnerability to CISA.
General Recommendations
As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms.
Additional Resources
Terms of Use
Recommended Practices
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolating them from business networks.
When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
Advisory Conversion Disclaimer
This ICSA is a verbatim republication of Siemens ProductCERT SSA-970803 from a direct conversion of the vendor's Common Security Advisory Framework (CSAF) advisory. This is republished to CISA's website as a means of increasing visibility and is provided "as-is" for informational purposes only. CISA is not responsible for the editorial or technical accuracy of republished advisories and provides no warranties of any kind regarding any information contained within this advisory. Further, CISA does not endorse any commercial product or service. Please contact Siemens ProductCERT directly for any questions regarding this advisory.
Revision History
Initial Release Date: 2026-11-10
Date
Revision
Summary
2026-11-10
1
Publication Date
2026-11-17
2
Initial CISA Republication of Siemens ProductCERT SSA-970803 advisory
Legal Notice and Terms of Use
Source: CISA Cybersecurity Advisories